Appearance | |||
Transmission distance | |||
Model | F92A-C-1 2M | ||
Model | F92A-C-1 | ||
Transmission distance | 5 mm (Refer to Safety Precautions on Data Sheet.) | ||
Set transmission distance | 0 to 4.5 mm | ||
Response time | 1 ms max. | ||
Ambient temperature | Operating/Storage: -25 to 70°C (with no icing and condensation) | ||
Ambient humidity | Operating/Storage: 35% to 95% (with no condensation) | ||
Insulation resistance | 50 MΩ min. (at 500 VDC) between lead wires and case | ||
Dielectric strength | 1,000 VAC, 50/60 Hz for 1 minute between lead wires and case | ||
Vibration resistance (destruction) | 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions | ||
Shock resistance (destruction) | 1,000 m/s2 10 times each in X, Y, and Z directions | ||
Degree of protection | IEC IP67, in-house standard for oil resistance | ||
Connection method | Pre-wired Models (Standard cable length: 2 m) | ||
Transmittable Proximity Sensors * | E2E-X5E1, -X5E2, -X5F1, -X5F2, -X5Y1, -X5Y2 E2E2-X5C1, -X5C2, -X5Y1, -X5Y2 E2F-X5E1, -X5E2, -X5F1, -X5F2, -X5Y1, -X5Y2 |
||
Weight (packed state) | Approx. 160 g | ||
Materials | Case | Brass | |
Sensing surface | ABS |