Omron Proximity Sensors. Rectangular. E2Q6

Rectangular Proximity Sensor
E2Q6

Freely Change the Sensing Direction

DC Models

Shielded/
Unshielded
Sensing distance Connection method Operation mode Model
NPN output PNP output
Shielded
3454_1_1
20 mm Terminal block NO + NC E2Q6-N20E3-H E2Q6-N20F3-H
Unshielded
3454_1_2
30 mm E2Q6-N30ME3-H E2Q6-N30MF3-H

Accessories (Sold Separately)

Recommended Cable Gland (ST Type) (Manufactured by LAPP)

Purchase a cable gland to maintain a water-resistant structure.

Product number
Color Screw size Applicable cable outer diameter
ST-M20 × 1.5 Black M20 × P1.5 7 to 13 dia.
Applicable seal packing
GPM20
Note: Purchase a seal packing to maintain water resistance.
For details or to make purchases, contact your OMRON sales representative.

Shielding
Shielded Unshielded
Model E2Q6-N20Ƴ-H E2Q6-N30MƳ-H
Sensing distance 20 mm ±10% 30 mm ±10%
Set distance 0 to 16 mm 0 to 24 mm
Differential travel 15% max. of sensing distance
Detectable object Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data (Reference Value) on Data Sheet.)
Standard sensing object Iron, 60 × 60 × 1 mm Iron, 90 × 90 × 1 mm
Response frequency *1 150 Hz 100 Hz
Power supply voltage
(operating voltage range)
10 to 30 VDC, including 10% ripple (p-p)
Current consumption 20 mA max.
Control output Load current 200 mA max.
Residual voltage 2 V max. (at 200 mA load current)
Indicators Power indicator (green), detection indicator (yellow)
Operation mode NO + NC
Protection circuits Power supply reverse polarity protection, output reverse polarity protection, and load short-circuit protection
Ambient temperature range Operating and storage: -25 to 70°C (with no icing or condensation)
Ambient humidity range Operating and storage: 35% to 95% (with no condensation)
Temperature influence ±15% max. of sensing distance at 23°C in the temperature range of -25 to 70°C
Voltage influence ±2% max. of sensing distance at 24 VDC in the range of 24 VDC ±15%
±2% max. of sensing distance at 12 VDC in the range of 12 VDC ±15%
Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength 1,000 VAC, at 50/60 Hz for 1 min. between current-carrying parts and case
Vibration resistance (destruction) 10 to 55 Hz with a 1.5-mm double amplitude in X, Y, and Z directions
Shock resistance (destruction) 300 m/s2 3 times each in six directions
Degree of protection IEC IP67 *2
Connection method Terminal block
Weight (packed state/Sensor only) Approx. 250 g/approx. 230 g
Materials Case Polyamide (PA)
Sensing surface Polyamide (PA)
Terminal base Polyamide (PA)
Accessories Instruction manual
*1. The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and a set distance of half the sensing distance.
*2. When the recommended cable gland is used.

Sensors

E2Q6-N20E3-H
E2Q6-N20F3-H
E2Q6-N30ME3-H
E2Q6-N30MF3-H

E2Q6 Dimensions 3

Accessories (Sold Separately)

Recommended Cable Gland (ST Type) (Manufactured by LAPP)

E2Q6 Dimensions 5